4-3-19 E463 : OLP protection control caused comp. down
Outdoor unit display E463
Criteria
•OLPSENSORtempaboveTrip_Dis.
Cause of problem
•Seeifthesubvalveisopen.
•Checktheamountofcoolant.
•ChecktheOLPsensor.
1. How to check
No
No
No
No
No
Yes
Yes
Yes
Check the amount of coolant.
The sensor's resistance normal?
(Refer to E20.)
The outdoor/indoor EEV operates normally?
All the sub valves open?
Clogging in the pipeline?
(ex-filter)
Test operation
Replace the OLP sensor
Connect S-net to vacuum. (forceful)
Open the sub valve.
Check the EEV.
Check the pipeline.