Installation Procedure
Additional refrigerant
H/P H/R
Ø12.70 (5 m)
Ø12.70 (5 m)
Ø12.70 (5 m)
Ø6.35 (5 m)
Ø6.35 (10 m)
Ø6.35 (15 m)
Ø9.52 (10 m)
Ø9.52 (10 m)
Ø9.52 (10 m)
Ø9.52
(10 m)
Ø6.35 (5 m)
Ø9.52 (10 m)
46.4kW
4.5kW
5.6kW
5.6kW
7.1kW
7.1kW
7.1kW
7.1kW
3.6kW
Ø9.52 (1m)
Ø12.70 (5 m)
Ø15.88 (10 m)
Ø12.70 (10 m)
Ø9.52
(15 m)
Ø9.52
(10 m)
Ø12.70 (10 m)
Ø9.52 (18 m)
Ø9.52
(18 m)
Ø9.52 (25 m)
Ø9.52
(15 m)
Ø9.52
(10 m)
MCU
MCU
Ø6.35(2 m)
2.8kW
7.1kW
11.2kW
7.1kW
11.2kW
7.1kW
7.1kW
7.1kW
Ø6.35(15 m)
61.6 kW (33.6 kW + 28.0 kW)
Refrigerant pipe installation
Basic amount of refrigerant within the outdoor unit (kg)
Amount of additional refrigerant has to be calculated based on the sum of all liquid pipe length.
Classification AM080AXVGGH/EU AM100AXVGGH/EU AM120AXVGGH/EU AM140AXVGGH/EU AM160AXVGGH/EU AM180AXVGGH/EU
Basic amount 7. 0 7. 0 7. 0 8.0 10.5 10.5
Classification AM200AXVGGH/EU AM220AXVGGH/EU AM240AXVGGH/EU AM260AXVGGH/EU
Basic amount 10.5 10.5 14 14
Classification AM080AXVAGH/EU AM100AXVAGH/EU AM120AXVAGH/EU AM140AXVAGH/EU AM160AXVAGH/EU AM180AXVAGH/EU
Basic amount 5.5 5.5 7. 0 7. 0 8.0 8.0
Classification AM200AXVAGH/EU AM220AXVAGH/EU AM240AXVAGH/EU AM260AXVAGH/EU
Basic amount 10.5 10.5 14.0 14.0
Classification AM100AXVDGH/EU AM120AXVDGH/EU AM140AXVDGH/EU AM160AXVDGH/EU AM180AXVDGH/EU
Basic amount 5.5 7. 0 7. 0 8.0 8.0
Classification AM080AXVGGR/EU AM100AXVGGR/EU AM120AXVGGR/EU AM140AXVGGR/EU AM160AXVGGR/EU AM180AXVGGR/EU
Basic amount 7. 0 7. 0 7. 0 8.0 10.5 10.5
Classification AM200AXVGGR/EU AM220AXVGGR/EU AM240AXVGGR/EU AM260AXVGGR/EU
Basic amount 10.5 10.5 14.0 14.0
Amount of additional refrigerant depending on the pipe size ( )
Amount of additional refrigerant has to be calculated based on the sum of all liquid pipe length.
Size of liquid pipe Ø 6.35 Ø 9.52 Ø 12.70 Ø 15.88 Ø 19.05 Ø 22.22 Ø 25.40 Ø 28.58
Additional amount
(kg/m)
0.02 0.06 0.125 0.18 0.27 0.35 0.53 0.65
Amount of
refrigerant added
when the diameter
of liquid pipe is
reduced (kg/m)
- 0.08 0.13 0.195 0.28 0.42 0.53 -
For the indoor unit already connected to EEV kit, the additional refrigerant charging is 0.01kg per meter regardless of the pipe size.