6
Preparations for Outdoor Unit
English
Installation Procedure
Premium energy efficiency type (Heat Pump)
Model name for
combination
Number of
individual
outdoor units
Total capacity of the
connected indoor units
Maximum number
of connectable
indoor units
Combined outdoor units
AM***AXVGGH
Minimum
(kW)
Maximum
(kW)
080 100 120 140 160 180 200 220 240 260
AM080AXVGGH 1 11.2 29.1 14 1
AM100AXVGGH 1 14.0 36.4 18 1
AM120AXVGGH 1 16.8 43.7 21 1
AM140AXVGGH 1 19.6 51.0 26 1
AM160AXVGGH 1 22.4 58.2 29 1
AM180AXVGGH 1 25.2 65.5 32 1
AM200AXVGGH 1 28.0 72.8 36 1
AM220AXVGGH 1 30.8 80.1 40 1
AM240AXVGGH 1 33.6 8 7. 4 43 1
AM260AXVGGH 1 36.4 94.6 47 1
AM280AXVGGH 2 39.2 101.9 51 1 1
AM300AXVGGH 2 42.0 109.2 54 1 1
AM320AXVGGH 2 44.8 116.5 58 1 1
AM340AXVGGH 2 4 7. 6 123.8 61 1 1
AM360AXVGGH 2 50.4 131.0 64 2
AM380AXVGGH 2 53.2 138.3 64 1 1
AM400AXVGGH 2 56.0 145.6 64 2
AM420AXVGGH 2 58.8 152.9 64 1 1
AM440AXVGGH 2 61.6 160.2 64 1 1
AM460AXVGGH 2 64.4 167.4 64 1 1
AM480AXVGGH 2 6 7. 2 174.7 64 1 1
AM500AXVGGH 2 70.0 182.0 64 1 1
AM520AXVGGH 2 72.8 189.3 64 2
AM540AXVGGH 3 75.6 196.6 64 1 1 1
AM560AXVGGH 3 78.4 203.8 64 1 1 1
AM580AXVGGH 3 81.2 211.1 64 1 1 1
AM600AXVGGH 3 84.0 218.4 64 1 1 1
AM620AXVGGH 3 86.8 225.7 64 1 2
AM640AXVGGH 3 89.6 233.0 64 1 2
AM660AXVGGH 3 92.4 240.2 64 2 1
AM680AXVGGH 3 95.2 2 47. 5 64 1 1 1
AM700AXVGGH 3 98.0 254.8 64 1 2
AM720AXVGGH 3 100.8 262.1 64 1 2
AM740AXVGGH 3 103.6 269.4 64 1 2
AM760AXVGGH 3 106.4 276.6 64 1 2
AM780AXVGGH 3 109.2 283.9 64 3
AM800AXVGGH 4 112.0 291.2 64 1 2 1
AM820AXVGGH 4 114.8 298.5 64 1 2 1
AM840AXVGGH 4 117.6 305.8 64 1 2 1
AM860AXVGGH 4 120.4 313.0 64 3 1
AM880AXVGGH 4 123.2 320.3 64 2 2
AM900AXVGGH 4 126.0 327.6 64 1 1 2
AM920AXVGGH 4 128.8 334.9 64 2 2
AM940AXVGGH 4 131.6 342.2 64 1 1 2
AM960AXVGGH 4 134.4 349.4 64 1 3
AM980AXVGGH 4 137.2 356.7 64 1 3