53
A
ENGLISH
Extending the power cable
1. Prepare the following tools.
Tools Crimping pliers Connection sleeve Insulation tape Contraction tube
Spec MH-14
20xØ0.26 inch(6.5
mm)
(HxOD)
Width 0.75 inch(19
mm)
70xØ0.31 inch(8.0
mm)
(LxOD)
Shape
2. As shown in the gure, peel o the shields from the rubber
and wire of the power cable.
- Peel o 0.79 inch(20 mm) of cable shields from the pre-
installed tube.
t For information about the power cable specications for
indoor and outdoor units, refer to the installation manual.
t After peeling o cable wires from the pre-installed tube,
insert a contraction tube.
CAUTION
3. Insert both sides of core wire of the power cable into the
connection sleeve.
f Method 1
Push the core wire into the sleeve from both sides.
Connection sleeve
f Method 2
Twist the wire cores together and push it into the sleeve.
Connection sleeve
4. Using a crimping tool, compress the two points and ip it over and compress another two
points in the same location.
- The compression dimension should be 0.31 inch (8.0 mm).
- After compressing it, pull both sides of the wire to make sure it is rmly pressed.
Compression
dimension
f Method 1
Compress it 4 times.
0.20 inch
(5 mm)
f Method 2
Compress it 4 times.
0.20 inch
(5 mm)
Unit: inch(mm)
120
60
202020
180
Power cable
20
Pre-installed tube for the power cable
0.79 (20)
0.79 (20) 0.79 (20)
2.36 (60)
4.72 (120)
7.09 (180)
0.79 (20)