23
ENGLISH
02 series installation option(Detailed)
F4
F3
F1 F2
V2
V1
1(L) 2(N)
2
1
HOT
COIL
AC
POWER
OUTDOOR
COMMUNICATION
Wire Remote
Controller
DC 12V
* The output of hot coil terminal is AC 220 V / 230 V
(The same as Indoor Unit’s input Power)
COM1 COM2
(+) L N (-)
The external output of SEG15 is generated by MIM-B14 connection. (Refer to the manual of MIM-B14.)
Option SEG1 SEG2 SEG3 SEG4 SEG5 SEG6
Explanation PAG E MODE
Use of robot
cleaning
Use of external room temperature
sensor / Minimizing fan operation when
thermostat is o
Use of central control FAN RPM compensation
Remote
Controller
Display
Indication
and Details
Indication Details Indication Details Indication Details Indication
Details
Indication Details Indication Details
Use of
External
room
temperature
sensor
Minimizing fan
operation when
thermostat is o
0 2
0 Disuse
0
Disuse
Disuse
0 Disuse
0 Disuse
1 Use Disuse 1
RPM
compensation
1 Use
2
Disuse Use
(
*1
)
1 Use 2
High ceiling
KIT
3 Use
Use
(
*1
)
Option SEG7 SEG8 SEG9 SEG10 SEG11 SEG12
Explanation PAG E Use of drain pump
Use of hot water
heater
EEV Step when heating
stops
Remote
Controller
Display
Indication
and Details
Indication Details Indication Details Indication Details Indication Details Indication Details Indication Details
1
0 Disuse 0 Disuse 0
Default
value
1 Use 1
Use
(
*2
)
1
Noise
decreasing
setting
2
When an indoor
unit stops, drain
pump will operate
for 3min
2 --
3
Use
(
*2
)
The output of hot water heater in SEG9 is generated from the hot coil part of the terminal board in duct models.
Option No. : 02XXXX-1XXXXX-2XXXXX-3XXXXX