100
Optional item Input unit SEG1 SEG2 SEG3 SEG4 Function of the option Remarks
Channel address Main 1 3
A U
Automatic setting (Factory
default)
Address for classifying the
product from upper level
controller (DMS, S-NET 3, etc.)
0 ~ 15
Manual setting for channel
0~15
Snow
accumulation
prevention
control
Main 1 4
0 0 Enabled (Factory default)
During snow accumulation,
the fan may spin even when
the unit is not in operation
0 1 Disabled
Unused option Main 1 5 0 0 Unused option Unused option by this model
Unused option Main 1 6 0 0 Unused option Unused option by this model
Speed operation Main 1 7
0 0 Disabled (Factory default)
Enabling this setting will
command the air conditioner
to cool/heat faster at initial
start-up.
However, this function will
not work when High-head
condition setting or Long-
piping condition setting is
enabled.
0 1 Enabled
Max. capacity
restriction
(B type PBA)
Main 1 8
0 0 Enabled (Factory default)
Restrict excessive capacity
increase when operating
indoor units with small
capacity
0 1 Disabled
Gas leak
pump down
(B type PBA)
Main 1 9
0 0 Disabled (Factory default)
If the gas leak occurred it
should be entered in the
pump down operation.
0 1 Enabled
Unused option Main 2 0 0 0 Unused option
Unused option by this model
LA KIT option
(B type PBA)
Main 2 1
0 0 Disabled (Factory default)
Set when LA KIT is installed.
0 1 Enabled
Emergency
operation for
indoor unit
communication
error
(B type PBA)
Main 2 2
0 0 Disabled (Factory default)
When set, emergency
operation is possible even if an
indoor communication error
occurs.
0 1
Indoor high humidity
condition (operating for up
to 12hours)
0 2
Indoor low humidity
condition (operating for up
to 24hours)
There is a risk of water leakage during emergency operation for indoor unit communication error. Please be careful
when using it.
Setting outdoor unit option switch and key function