102
K2 (Number of
press)
KEY operation Display on segment
1 time Refrigerant charging in Cooling mode “K” “5” “BLANK” “BLANK”
2 times Trial operation in Cooling mode “K” “6” “BLANK” “BLANK”
3 times Pump down all units in Cooling mode “K” “7” “BLANK” “BLANK”
4 times
H/R: Checking the pipe connection
H/P: Automatic setting of operation mode (Cooling/
Heating) for trial operation
“K” “8” “BLANK” “BLANK”
5 times Checking the amount of refrigerant
“K” “9” X X (Display of last two digits may dier
depending on the progress)
6 times Discharge mode of DC link voltage “K” “A” “BLANK” “BLANK”
7 times Forced defrost operation “K” “B” “BLANK” “BLANK”
8 times Forced oil collection “K” “C” “BLANK” “BLANK”
9 times Inverter compressor 1 check “K” “D” “BLANK” “BLANK”
10 times Inverter compressor 2 check “K” “E” “BLANK” “BLANK”
11 times Fan 1 check “K” “F” “BLANK” “BLANK”
12 times Fan 2 check “K” “G” “BLANK” “BLANK”
13 times
A type PBA End key operation
B type PBA
H/R : Auto pipe pairing,
H/P : Unused
“K” “H” X X (Display of last two digits may dier
depending on the progress)
14 times B type PBA End key operation
During "Discharge mode of DC link voltage", voltage of INV1 and INV2 will be displayed alternately.
Even when the outdoor unit power is o, it is dangerous when you come in contact with inverter PCB and fan PCB
since they are charged with high DC voltage.
When pressing K2 key 9 to 12 times without inverter checker, error code can be displayed on segment even though
the outdoor unit is normal.
When replacing/repairing the PCB, cut-o the power and wait until the DC voltage is discharged before replacing/
repairing them. (Wait for more than 15 minutes to allow it to discharge naturally.)
When there were error, 'Discharge mode of DC link voltage' may not have been eective. Especially if error E464
and E364 have been occurred, power element might be damaged by re and therefore, do not use the 'Discharge
mode of DC link voltage'.
If the 1st-generation MCU is installed, the Auto pipe pairing operation can not be used.
If the 2nd-generation MCU is installed, the Checking the pipe connection can not be used.
- 1st-generation MCU : MCU-S*NEE*N, MCU-S2NEK1N
- 2nd-generation MCU : MCU-S*NEK2N,MCU-S4NEK3N,MCU-S1NEK1N
If there is an A type PBA among the outdoor units installed as a module, the Auto pipe pairing operation can not
be used.
K3 (Number of
press)
KEY operation Display on segment
1 time Initialize (Reset) setting Same as initial state
Setting outdoor unit option switch and key function