46
Refrigerant pipe installation
Additional refrigerant
H/P H/R
Ø12.70 (5 m)
Ø12.70 (5 m)
Ø12.70 (5 m)
Ø6.35 (5 m)
Ø6.35 (10 m)
Ø6.35 (15 m)
Ø9.52 (10 m)
Ø9.52 (10 m)
Ø9.52 (10 m)
Ø9.52 (10 m)
Ø6.35 (5 m)
Ø9.52 (10 m)
46.4kW
4.5kW
5.6kW
5.6kW
7.1kW
7.1kW
7.1kW
7.1kW
3.6kW
Ø9.52 (1m)
Ø12.70 (5 m)
Ø15.88 (10 m)
Ø12.70 (10 m)
Ø9.52 (15 m)
Ø9.52 (10 m)
Ø12.70 (10 m)
Ø9.52 (18 m)
Ø9.52 (18 m)
Ø9.52
(25 m)
Ø9.52
(15 m)
Ø9.52
(10 m)
MCU
MCU
Ø6.35(2 m)
2.8kW
7.1kW
11.2kW
7.1kW
11.2kW
7.1kW
7.1kW
7.1kW
Ø6.35(15 m)
61.6 kW (33.6 kW + 28.0 kW)
Refrigerant pipe installation
Basic amount of refrigerant within the outdoor unit (kg)
- Amount of additional refrigerant has to be calculated based on the sum of all liquid pipe length.
Classication
AM080XVAG AM100XVAG AM120XVAG AM140XVAG AM160XVAG AM180XVAG
Basic type 5.5 5.5 6.5 7.7 7.7 8.4
Classication
AM200XVAG AM220XVHG AM240XVAG AM260XVAG AM080XVHG AM100XVHG
Basic type 8.4 8.4 14.3 14.3 6.5 6.5
Classication
AM120XVHG AM140XVHG AM160XVHG AM180XVHG AM200XVHG AM220XVHG
Basic type 6.5 7.7 7.7 8.4 8.4 8.4
Amount of additional refrigerant depending on the pipe size (ⓐ)
- Amount of additional refrigerant has to be calculated based on the sum of all liquid pipe length.
Size of liquid pipe Ø 6.35 Ø 9.52 Ø 12.70 Ø 15.88 Ø 19.05 Ø 22.22 Ø 25.40 Ø 28.58
Additional amount (kg/m) 0.02 0.06 0.125 0.18 0.27 0.35 0.53 0.65
- For the indoor unit already connected to EEV kit, the additional refrigerant charging is 0.01kg per meter
regardless of the pipe size.
DVM S HE_IM_DB68-05461A-08_EN.indd 46 2017-03-24 오후 1:38:21