Caution for welding the pipe to an outdoor unit
When welding the pipe, the unit may get damaged by the heat and ame from welding. Use a ame
proong cloth to protect the unit from a welding re or ame. Sensor for detecting outside temperature is
located on the left side of the welding part so be extra careful not to damage the sensor when welding.
The O-ring and Teon packing inside service valve may get damaged by the heat from welding. Wrap
the bottom side of the service valve with a wet cloth and weld it as shown in the illustration. Also, water
dripping from the wet cloth may interrupt the welding. Make sure the water does not drip from the wet
cloth.
Make sure that connected pipes does not interrupt each other or make contact with the product.
(Vibration may cause damage to the pipes.)
When removing the sealed pipe on the bottom side of the service valve, cut it with a pipe cutter rst
and then start the welding. When the sealed pipe is welded without cutting, you may get injured by the
refrigerant within the pipe.
Temperature
sensor
Wet towel
Service port
Service valve
< H/R >< H/P >
Temperature
sensor
Wet towel
Service port
Service valve
CAUTION