Classication Example Remarks
Maximum
allowable
height
dierence of
pipe
Outdoor unit ~
Indoor unit
110/110m
Note 2)
H1 ≤ 110/110m
Indoor unit ~
Indoor unit
50m or less H2 ≤ 50m
But, when AMNQDEH / AMJNV is installed, H2 is 15 m or less.
Maximum
allowable
length after
branch joint
First branch
joint ~ Farthest
Indoor unit
Pipe length
45 m or less
Installing only with Y-joint
b+c+d+e+f+g+p ≤ 45 m
-
Installing with Y-joint and
distribution header
i+k ≤ 45 m
Installing only with distribu-
tion header
i ≤ 45 m
45 m~90m
Note 1)
Required conditions must be satised
-
EEV kit Model name Remarks
EEV kit ~
Indoor unit
Actual pipe
length
2 m
MEV-E24SA
1 indoor
Apply to products without EEV
(Wall mount & ceiling)
MEV-E32SA
20 m or less
MXD-E24K132A
2 indoorMXD-E24K200A
MXD-E32K200A
MXD-E24K232A
3 indoor
MXD-E24K300A
MXD-E32K224A
MXD-E32K300A
Please refer to the EEV Kit manual.
Note 1) Required condition
Classication Condition Example
First branch joint ~
Farthest Indoor unit
45m ≤ b+c+d+e+f+g+p ≤ 90m: branch pipes
(b, c, d, e, f, g) size must be increased by 1 grade
Total length of
extended pipe
If the size of pipe (main pipe), between the
rst branch joint and the outdoor unit, is not
increased by 1 grade, a+(b+c+d+e+f+g)×2
+h+i+j+k+l+m+n+p ≤ 1000 m
If the size of pipe (main pipe), between the
rst branch joint and the outdoor unit, is
increased by 1 grade, (a+b+c+d+e+f+g)×2
+h+i+j+k+l+m+n+p ≤ 1000 m
Each Y-joint ~
Each indoor unit
h, i, j, … p ≤ 45 m
Dierence between the distance of the outdoor unit to the farthest indoor unit
and nearest indoor unit ≤ 45m, (a+b+c+d+e+g+p)-(a+h) ≤ 45m
Note 2) When indoor unit is located at higher level than outdoor unit, allowable height dierence is 110m, (If the
height dierence is over 40m, contact your local dealer for more information.)
but when the indoor unit is located at lower level than outdoor unit, allowable height dierence is 110m (If the
height dierence is over 50m, need to decide whether to install PDM kit or not.)
Model name of the PDM kit : MXD-A38K2A, MXD-A12K2A, MXD-A58K2A