64
Refrigerant pipe installation
3. Install the distribution header horizontally.
Install the distribution header horizontally so that its ports does not face down.
Below ±10°
Horizon line
Socket Distribution header
Pipe
(Separately purchased item)
Below ±15°
Horizon line
Horizon line
< Liquid side >
Below ±15°
Horizon line
Below ±10°
Horizon line
< Gas side >
Installing the branch joint between outdoor units
Installation of outdoor joints
Do not install the outdoor
joint in this direction.
Liquid pipe
High pressure
gas pipe
Gas pipe
High pressure gas pipe only applies to the H/R product.