72
Electrical wiring work
High EER module (Heat recovery)
Model MCA MFA
AM240JXVHGR1 50.0 63
AM260JXVHGR1 50.0 63
AM280JXVHGR1 57.0 63
AM300JXVHGR1 64.1 75
AM320JXVHGR1 67.5 75
AM340JXVHGR1 69.5 80
AM360JXVHGR1 69.5 80
AM380JXVHGR1 76.5 90
AM400JXVHGR1 85.0 100
AM420JXVHGR1 87.0 100
AM440JXVHGR1 89.0 100
AM460JXVHGR1 94.5 125
AM480JXVHGR1 94.5 125
AM500JXVHGR1 101.5 125
AM520JXVHGR1 108.6 125
AM540JXVHGR1 112.0 125
AM560JXVHGR1 114.0 125
AM580JXVHGR1 114.0 125
AM600JXVHGR1 121.0 150
AM620JXVHGR1 129.5 150
AM640JXVHGR1 131.5 150
AM660JXVHGR1 133.5 150
AM680JXVHGR1 139.0 175
AM700JXVHGR1 139.0 175
AM720JXVHGR1 146.0 175
AM740JXVHGR1 153.1 175
AM760JXVHGR1 156.5 175
AM780JXVHGR1 158.5 175
AM800JXVHGR1 158.5 175
When installing outdoor units in module, select the power supply cable according to the sum of outdoor unit
capacity. (Refer to the table for each model)
Power Supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed
exible cord. (Code designation IEC:60245 IEC 66 / CENELEC: H07RN-F)
Ex.) AM500XVA
AM120XVA : 4 mm
2
AM280XVA : 16 mm
2
AM500XVA : 35 mm
2
①
②
③
AM220XVA AM160XVA AM120XVA
② ③①
ELCB
MCCB+ ELB
or
DVM S HE_IM_DB68-05461A-08_EN.indd 72 2017-03-24 오후 1:38:33