74
Electrical wiring work
Power and communication cable conguration
Main power and the ground cable must be withdrawn through the knock-out hole on the bottom-right or right
side of the cabinet.
Withdraw the communication cable from the designated knock-out hole on the bottom-right side of the front part.
Install the power and communication cable using separate cable protection tube.
Fix a protection tube to the knock-out hole on the outdoor unit by using a CD connector or bushing. Make sure to
use insulating bushing.
<When the module combination is in the tables of "Outdoor unit combination">
Main unit
Sub unit
Sub unit
ELCB
MCCB+
ELB
or
Communication cable
Power·ground cable
<When the module combination is not in the tables of “Outdoor unit combination”>
Main unit
Sub unit Sub unit
Ground cable Ground cableGround cable
Communication
cable
Power • ground
cable
Power cable Power cablePower cable
Communication
cable between
outdoor units
Communication
cable between
outdoor units
Protection
tube
ELCB
MCCB+
ELB
or
ELCB
MCCB+
ELB
or
ELCB
MCCB+
ELB
or
Communication cable between outdoor units Power cable
Protection tube Power/ground cable