8
Preparing for installation
Outdoor unit combination
Make sure to use an indoor unit that is compatible with DVM S.
Indoor units can be connected within the range indicated in following table.
If the total capacity of the connected indoor units exceeds the indicated maximum capacity, cooling and heating
capacity of the indoor unit may decrease.
Total capacity of the connected indoor units can be allowed from 50% to 130% of the total outdoor unit capacity.
0.5 × Σ(Outdoor unit capacity) ≤ Total capacity of the connected indoor units ≤ 1.3 × Σ(Outdoor unit capacity)
You can connect maximum 64 indoor units to the outdoor unit. Maximum quantity of connectable indoor unit is
set to 64 since outdoor unit only support up to 64 communication address. Indoor unit address can be assigned
from 0~63. If the indoor unit address was assigned from 64~79, E201 error will occur.
Maximum 32 Wall-mount type indoor units with EEV (AMFNQDEH, AMJNVDKH) can be connected.
Use the following table to determine the size and number of outdoor units needed to achieve thecapacity
requirements.
CAUTION
Standard type (Heat pump)
Model name for combination
AM080JXVAGH/EU AM100JXVAGH/EU AM120JXVAGH/EU AM140JXVAGH/EU AM160JXVAGH/EU
Number of individual outdoor units
1 1 1 1 1
Combined outdoor
unit
AM080JXVAGH
1
AM100JXVAGH
1
AM120JXVAGH
1
AM140JXVAGH
1
AM160JXVAGH
1
AM180JXVAGH
AM200JXVAGH
AM220JXVAGH
AM240HXVAGH
AM260HXVAGH
Rated capacity
Cooling (kW)
22.4 28.0 33.6 40.0 45.0
Heating (kW)
25.2 31.5 37.8 45.0 50.4
Total capacity of the
connected indoor
units (Cooling)
Minimum (kW)
11.2 14.0 16.8 20.0 22.5
Maximum (kW)
29.1 36.4 43.7 52.0 58.5
Maximum number of connectable
indoor units
14 18 21 26 29
DVM S HE_IM_DB68-05461A-08_EN.indd 8 2017-03-24 오후 1:38:15