Optional item Input unit SEG1 SEG2 SEG3 SEG4 Function of the option Remarks
Unused option Main 1 5 0 0 Unused option Unused option by this model
Unused option Main 1 6 0 0 Unused option Unused option by this model
Speed operation Main 1 7
0 0 Disabled (Factory default)
Enabling this setting will
command the air conditioner to
cool faster at initial start-up.
However, this function will not
work when High-head condition
setting or Long-piping condition
setting is enabled.
0 1 Enabled
Max. capacity
restriction
(B type PBA)
Main 1 8
0 0 Enabled (Factory default)
Restrict excessive capacity
increase when operating indoor
units with small capacity
0 1 Disabled
Gasleak
Pumpdown
(B type PBA)
Main 1 9
0 0 Disabled (Factory default)
If the gas leak occurred it should
be entered in the pumpdown
operation.
0 1 Enabled
Unused option Main 2 0 0 0 Unused option
Unused option by this model
LA KIT option
(B type PBA)
Main 2 1
0 0 Disabled (Factory default)
Set when LA KIT is installed.
0 1 Enabled
Emergency
operation for
indoor unit
communication
error (B type PBA)
Main 2
2
0 0 Disabled (Factory default)
When set, emergency operation
is possible even if an indoor
communication error occurs.
0 1
Indoor high humidity
condition (operating for up
to 12hours)
0 2
Indoor low humidity
condition (operating for up
to 24hours)
There is a risk of water leakage during emergency operation for indoor unit communication error. Please be careful when
using it.