Installation Procedure
Option SEG13 SEG14 SEG15 SEG16 SEG17 SEG18
Explanation PAGE Use of external control
Setting the output of
ʪуϩʪθɇʀͱϩθͱࢩkуϩʪθɇ
˵ʪɇϩʪθϑ˝ɇࢩAͱͱ˝
ͱΧʪθɇϩͱϑ˝ɇࢩ
Free Cooling control signal
S-Plasma ion Buzzer control Hours of filter usage
Indication
and Details
Indication Details Indication Details Indication Details Indication Details Indication Details Indication Details
2
0Disuse
Normal Signal
Control (*4)
0
External control
(Thermo On)
0Disuse0
Use
buzzer
2 1000 Hour
1
ĮĘࢩĮ
control
1
External control
(Operation On)
2
OFF
control
2
External heater
signal (*5)
3
Window
ĮĘࢩĮ
control
3
External heater
signal (*5)
8Disuse
Reverse Signal
Control (*4)
4
Cooling
operation signal
(*6)
1Use1
Disuse
buzzer
6 2000 Hour
9
ĮĘࢩĮ
control
5
Free Cooling
control (Cooling
Thermo On) (*7)
A
OFF
control
6
Free Cooling
ʀͱϩθͱ࣑Aͱͱ˝ࢩ
Dry Thermo
On) (*7)
B
Window
ĮĘࢩĮ
control
Option SEG19 SEG20 SEG21 SEG22 SEG23 SEG24
Explanation PAGE
Individual control of a remote
controller
²ʪɇϩ˝ϑʪϩϩ˝ʀͱΧʪϑɇϩͱࢩŵʪͱЭ˝
condensate water in heating mode
Adjusted EEV step of
stopped unit during
ͱθʪϩЇθࢩʒʪ˙θͱϑϩ
mode.
Motion detect sensor -
Indication and
Details
Indication
Details
Indication Details Indication
Details
Indication Details Indication Details
-
Heating Setting
Compensation
Removing
Condensate Water
in Heating Mode
3
0 or 1 channel 1
0 Default Disuse
0 Default
0Disuse
1 2 °C Disuse 1
Turn out in 30min.
without motion
2 channel 2
2 5 °C Disuse 2
Turn out in 60min.
without motion
3 Default Use (*8)
3
Turn out in 120min.
without motion
3 channel 3
4
Turn out in 180min.
without motion
4 2 °C Use (*8)
1
Adjusted
EEV
positon
5
Turn out in 30min.
without motion or
*advanced function
4 channel 4
6
Turn out in 60min.
without motion &
*advanced function
5 5 °C Use (*8)
7
Turn out in 120min.
without motion &
*advanced function
8
Turn out in 180min.
without motion &
*advanced function