Abnormal condition
Error
code
Indoor unit display indications
Ice
Blue
Yellow
Green
1. COND mid sensor is detached E241
XX
2. Refrigerant leakage (2nd detection) E554
3. Abnomally high temperature on Cond (2nd detection) E450
ߦ࢏øͱиΧθʪϑϑЇθʪϑࢩи࣑ߤʒʒʪϩʪʀϩͱ࣒ E451
5. Abnomally high temperature on discharged air on outdoor unit
(2nd detection)
E416
6. Indoor operation stop due to unconfirmed error on outdoor unit E559
7. Error due to reverse phase detection E425
8. Comp stop due to freeze detection (6th detection) E403
9. High pressure sensor is detached E301
10. Low pressure sensor is detached E306
11. Outdoor unit compression ratio error E428
12. Outdoor sump down_1 prevetion control E413
13. Compressor down due to low pressure sensor prevention
control_1
E410
ߣߦ࢏ƊЇϩɇʪͱЇϑͱΧʪ˝ͱ˙ʀͱͱ˝ࢩ˵ʪɇϩ˝đAƸƊĮøЭɇЭʪ
(1st detection)
E180
ߣߧ࢏ƊЇϩɇʪͱЇϑͱΧʪ˝ͱ˙ʀͱͱ˝ࢩ˵ʪɇϩ˝đAƸƊĮøЭɇЭʪ࣑ߤʒ
detection)
E181
Other outdoor unit self-diagnosis error that is not on the above list
Floating Switch (2nd detection) E153
XXX
EEPROM error E162
EEPROM option error E163
Error due to incompatible indoor unit E164
XXXX
: On, : Blinking, X : Off
࡛ If you turn off the air conditioner when the LED is flickering, the LED is also turned off.
࡛ If you re-operate the air conditioner, it operates normally at first, then detect an error again.
࡛ When E108 error occurs, change the address and reset the system.
Ex.) When address of the indoor unit #1 and #2 are set as 5, address of the indoor unit #1 will become 5 and indoor
unit #2 will display E108, A002.