EasyManua.ls Logo

Samsung AM TXMDCH Series - Page 19

Samsung AM TXMDCH Series
52 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
19
ENGLISH
Classification Y-joint connection Y-joint / EEV kit connection
Maximum
allowable
length of
pipe
Outdoor unit
~ Indoor
units
Actual
Length
The distance between the outdoor unit and the farthest indoor unit ≤ 150m (492’)
Ex) 8 indoor units
a+b+c+d+e+f+g+p≤ 150m (492’)
Ex) 6 indoor units
a+b+c+d+j ≤ 150m (492’)
Equivalent
length
The distance between an outdoor unit and the farthest indoor unit ≤ 175m (574’)
Main pipe
length
The main pipe(a) from the outdoor unit to the first Y-joint should be less than 110m
(361’).
Total
length
The sum of the total length of pipes should be less then 300m (984’).
Maximum
allowable
height
Outdoor unit
~ Indoor
units
Height H1: The difference of height between an outdoor unit and indoor unit < 50m (164’)
Height H2: The difference of height between indoor units ≤ 15m (49’)
Maximum allowable length
after Y-joint
Actual
Length
The distance between the first Y-joint and
the farthest indoor unit ≤ 40m (131’)
Ex) 8 indoor units
b+c+d+e+f+g+p≤ 40m (131’)
Allowable length between EEV kit and
an indoor unit ≤ 20m (65’)
Ex) h, l, j ≤ 20m (65’)
EEV Kit Model name Remarks
EEV Kit ~
Indoor units
Actual pipe lengh
2m (6.6’) or less
MEV-E24SA
1 indoor
Apply to products
without EEV (Wall
mounted & ceiling)
MEV-E32SA
20m (66’) or less
MXD-E24K132A
2 indoorMXD-E24K200A
MXD-E32K200A
MXD-E24K232A
3 indoor
MXD-E24K300A
MXD-E32K224A
MXD-E32K300A
When the equivalent length between an outdoor unit and the farthest indoor unit exceeds 90m (295’), upgrade the low
pressure pipe of the main pipe one step.
ki]_TW__]_hTWXptk}tGzGljvG䖐㨴㥐㛨ὤhhluUGGGX` YWYWTWZTY^GGG㝘䟸GYaX[aZW

Related product manuals