Troubleshooting
388 Samsung Electronics
4-4-64
,
:
Prohibition of the operation of Compressor due to Ooutdoor Temperature
1. How to check
The above error code is not caused by a product's problem but a function to protect the product by limiting the available tempera-
ture range so please refer to the usable temperature range in the product manual.
If the error code is displayed despite a condition that does not belong to any of the above diagnosis methods, read the temperature
sensor value of the outdoor inlet air with View Mode or S-net, and if the actual outdoor temperature is different, please replace the
temperature sensor.
Outdoor unit display
(prohibit heating operation in outdoor temperature over 30°C)
(prohibit heat filling operation in outdoor temperature over 15°C)
Indoor unit display
No sign
Criteria
:
Right before an outdoor unit starts heating operation by On signal of an indoor Remocon, the error
occurs and prohibits the operation in outdoor temperature over 30°C
:
Right before operating heat refrigerant filling mode by the K1 switch of an outdoor PCB, the error occurs
and prohibits the operation in outdoor temperature over 15°C
Cause of problem
• Operation Prohibition mode by the indoor temperature limit