Samsung Electronics 67
Model AE022MNADEH/EU AE028MNADEH/EU AE036MNADEH/EU
Power Supply Φ,#,V,Hz 1,220~240,50 1,220~240,50 1,220~240,50
Mode * HP / HR HP / HR HP / HR
Performance Capacity
Cooling*
kW 2.2 2.8 3.6
Btu/h 7,502 9,548 12,276
Heating*
kW 2.5 3.2 4.0
Btu/h 8,525 10,912 13,640
Power
Power Input
Cooling W 15 * 16 * 20 *
Heating W 18 * 24 * 28 *
Current Input
Cooling A 0.13 * 0.13 * 0.15 *
Heating A 0.15 * 0.19 * 0.20 *
Fan
Motor
Type - Crossflow Fan 83*L552 Crossflow Fan 83*L552 Crossflow Fan 98*L633
Output W 27 27 27
Number of unit 1 1 1
Airflow Rate
Cooling(High)
᎑/mim
4.50 * 5.70 * 7.10 *
Heating(High)
᎑/mim
6.00 * 8.50 * 10.00 *
Piping
Connections
Liquid Pipe
Φ,᎖ 6.35 6.35 6.35
Φ,inch 1/4
כ 1/4כ 1/4כ
Gas Pipe
Φ,᎖ 12.70 12.70 12.70
Φ,inch 1/2כ 1/2כ 1/2כ
Drain Pipe Φ,᎖ ID 18 HOSE ID 18 HOSE ID 18 HOSE
Field Wiring
Power Source Wire
Below 20m/
over 20m"
mm2 1.5 ~ 2.5 1.5 ~ 2.5 1.5 ~ 2.5
Transmission Cable mm2 0.75 ~ 1.50 0.75 ~ 1.50 0.75 ~ 1.50
Refrigerant
Type - R410A R410A R410A
Control Method - EEV INCLUDED EEV INCLUDED EEV INCLUDED
Sound Sound Pressure* High/Mid/Low dBA 33/29/25 36/31/26 37/33/29
Dimensions
Net Weight
Ꭰ
8.1 8.2 9.8
Shipping Weight
Ꭰ
9.7 9.8 11.7
Net Dimensions (W x Hx D)
᎖
750*250*242 750*250*242 826*275*260
Shipping Dimensions (W x Hx D)
᎖
800*302*298 800*302*298 886*335*317
Functions
Auto Restart - O O O
Auto Swing - O O O
Group/Individual Control - O O O
External Contact Control - O O O
Trouble Shooting by LED - O O O
Standard
Accessories
Installation Manual - O O O
Operation Manual - O O O
Pattern Sheet for Installation - X X X
Flexible Drain Hose - O O O
Filter / Safety Grille - Filter (Washable) Filter (Washable) Filter (Washable)
Wireless Remote Controller MR-EH00 MR-EH00
MR-EH00
Optional
Accessories
Wireless Remote Controller - - - -
Wired Remote
Controller
Simplified - MWR-WE10N MWR-WE10N MWR-WE10N
External Contact Interface Module - MIM-B14 MIM-B14 MIM-B14
*1) Mode
- HP : Heat Pump, HR : Heat Recovery
*2) Nominal cooling capacities are based on;
- Indoor temperature : 27˚C DB, 19˚C WB
- Outdoor temperature : 35˚C DB, 24˚C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m
*3) Nominal heating capacities are based on;
- Indoor temperature : 20˚C DB, 15˚C WB
- Outdoor temperature : 7˚C DB, 6˚C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m
*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.
*5) Specifications may be subject to change without prior notice for product improvement.
Indoor Unit (cont.)
Ŷ EHS TDM PLUS -Wall Monuted type