Troubleshooting
54
Samsung Electronics
4-4-5 Indoor EVAP OUT sensor Error (Open/Short)
1. How to check
Is indoor EVAP OUT sensor
connector separated from the PCB?
At that time,
is the resistance value significantly deviated
from the temp. table?
After separating indoor EVAP OUT sensor
connector from the PCB, measure the resistance
values between both terminals
Re-start after replacing PCB.
Re-start after connecting
the connector to the PCB.
As it is due to an
indoor EVAP OUT sensor defect, replace it.
Yes
Yes
Yes
No
No
Part to measure resistance value
Temperature
(°C)
Resistance
(KΩ)
70
60
50
40
30
21
10
0
-10
2.2
3.0
4.2
5.8
8.3
12.1
18.0
27.3
43.0
Outdoor unit display
x x x
(
x x x
:
The address of the error occurred indoor unit)
Indoor unit display
Operation Timer
Criteria
Refer to how to determine below
Cause of problem
The EVAP out sensor of No. XXX indoor unit has defective OPEN/SHORT