EasyManua.ls Logo

Samsung AM022FN1DEH/TK - 3-Phase Input Wiring Error

Samsung AM022FN1DEH/TK
334 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Troubleshooting
4-102 Samsung Electronics
1.
Cause of problem
4-4-58 3-phase Input Wiring error
Outdoor unit display
Indoorunit display
×(Operation) (Reservation) (Blast) (Filter) ×(Defrost)
Judgment Method
. When turn on the power and check the status of the power from the inverter .
If the phase does not connect the power(no phase) : E425 or E466 (E366) is displayed (Air conditioner to maintain
the normal state.)
However) N-phase must be pr operly connected.
Cause of problem
 Check the input wiring
 EMI Fuse short
Replace Inverter PCB
Power Off
Yes
Yes
No
Yes
Did the Main
Terminal Block and Power R, S, T, N is
connected properly?
Power BOX Terminal : Check the phase-to-phase
connection 380V of the R, S, T and then restart.
(N-phase must be properly connected.)
No
No
No
Yes
Connection and then restart it
Low voltage error during this initial charge :
Replace Fuse, if the rectifier diode of the inverter
PCB is normal.
Connection and then restart it
Did the Reactor
C
onnection Terminal is connected
properly?
Did the EMI PCB Fuse is short?
Is EMI PCB CN21
connector and Inverter PCB accurately
connected?

Table of Contents

Related product manuals