2-26 Samsung Electronics
Indoor Unit(cont.)
QGD-S(Big Duct)
Model AM180JNHPKH/TK AM224JNHPKH/TK
Power Supply ø/V/Hz 1/220-240/50 1/220-240/50
Mode*
1)
HP / HR HP / HR
Performance
Capacity
Cooling*
2)
kW 18.0 22.4
Btu/h 61,400 76,400
Heating*
3)
kW 20.0 25.0
Btu/h 54,300 67,600
Condensate (with High fan speed) Liters/h - -
Power
Input W 340 530
Running Current A 1.9 2.9
Sound Level Sound Pressure (High/Low)*
4)
dB(A) 42 44
Fan
Type - Sirocco Fan Sirocco Fan
Motor
Model - DL-17860SSBA DL-17860SSBA
Type - BLDC BLDC
Output W
Airflow Rate
High/Mid/Low m
3
/min 58/50/43 72/61/50
External Static Pressure
Standard(Min.~Max)
mmH2O 7.34(5-20) 7.34(5-20)
Refrigerant
Type - R410A R410A
Control Method - EEV EEV
Temperature Control - Micom&Thermistors Micom&Thermistors
Safety Devices - Fuse Fuse
Piping
Connections
Liquid (Flare) ø, mm 9.52 9.52
Gas (Flare) ø, mm 19.05 19.05
Drain ø, mm VP25(OD25, ID20) VP25(OD25, ID20)
Weight
Net Weight kg 82.5 82.5
Shipping Weight kg 92 92
Dimensions
Net Dimensions (W x H x D) mm 1350 x 910 x 450 1350 x 910 x 450
Shipping Dimensions (W x H x D) mm 1612 x 984 x 519 1612 x 984 x 519
Functions
Auto Restart - O O
Auto Swing - X X
Group/Individual Control - O O
External Contact Control - O O
Trouble Shooting by LED - X X
Standard
Accessories
Installation Manual - O O
Operation Manual - O O
Pattern Sheet for Installation - O O
Flexible Drain Hose - O O
Filter / Safety Grille - X X
Optional
Accessories
Wireless Remote Controller - MR-DH00 MR-DH00
Duct Receiver
Kits
Receiver
- MRK-A10 MRK-A10
Receiver Wire
- MRW-10A MRW-10A
Wired Remote
Controller
Simplified - MWR-WE10N MWR-WE10N
External Contact Interface Module - MIM-B14 MIM-B14
Drain Pump -
MDP-G075SQ
(Internal installation)
MDP-G075SQ
(Internal installation)
MDP-G075SP
(External installation)
MDP-G075SP
(External installation)
*1) Mode
- HP : Heat Pump, HR : Heat Recovery
*2) Nominal cooling capacities are based on;
- Indoor temperature : 27˚C DB, 19˚C WB
- Outdoor temperature : 35˚C DB, 24˚C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m
*3) Nominal heating capacities are based on;
- Indoor temperature : 20˚C DB, 15˚C WB
- Outdoor temperature : 7˚C DB, 6˚C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m
*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.