Troubleshooting
4-18 Samsung Electronics
Option SEG19 SEG20 SEG21 SEG22 SEG23 SEG24
Explanation PAGE
Individual control of a
remote controller
Heating setting compen-
sation
EEV Step of stopped unit
during oil return/defr ost
mode
Motion detect sensor -
Remote
Controller
Display
Indication
and Details
Indication Details Indication Details Indication Details Indication Details Indication Details
3
0 or 1 channel 1 0 Disuse
(*4)
0
Default
value
0 Disuse
1
Turn out in 30min.
without motion
2 channel 2 1 2 °C(35.6 °F)
1
Oil return
or Noise
decreasing
in defrost
mode
2
Turn out in 60min.
without motion
3 channel 3
25 °C(41 °F)
3
Turn out in 120min.
without motion
4
channel 4
4
Turn out in 180min.
without motion
5
Turn out in 30min.
without motion or
*advanc ed function
6
Turn out in 60min.
without motion or
*advanc ed function
7
Turn out in 120min.
without motion or
*advanc ed f
unction
8
Turn out in 180min.
without motion or
*advanc ed function
*
Advanced function: Controlling cooling/heating current or pow er saving with motion detect.
(*1)
Minimizing fan operation when thermostat is o
- Fan is turned oin cool mode / Fan operates for 20 seconds at an interval of 5 minutes in
heat mode .
(*2)
1: Fan is turned on continually when the hot water heater is turned on,
3: Fan is turned owhen the hot water heater is turned on with cooling only indoor unit
(*3)
When the following 2 or 3 is used as external heater On/Osignal, the signal for monitoring external contact control will not be
output.
2: Fan is turned on continually when the external heater is turned on,
3: Fan is turned owhen the external heater is turned on with cooling only indoor unit
If Fan is set to ofor cooling only indoor unit by setting the SEG9=3 or SEG15=3, you need to use an external sensor or wired r emote
controller sensor to
detect indoor temperature exactly.
(*4)
Default setting value
- 4Way Cassette , Mini 4Way Cassette: 5 °C
- Other indoor units: 2 °C
Air Flow
Suction side Discharge side
Electronic heater should
not be installed.
t Do not install the electronic heater in theow channel of the indoor unit fan.
CAUTION
Duct Indoor unit