EasyManua.ls Logo

Samsung AM036 - Cond Out Temperature Sensor Error (Open;Short)

Samsung AM036
344 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Troubleshooting
4-78 Samsung Electronics
1.
Cause of problem
4-4-39 Cond Out Temperature Sensor Error (Open/Short)
(Operation) ×(Reservation) (Blast) ×(Filter) ×(Defrost)
Disconnection or breakdown of relevant sensor .
Refer to the judgment method below.
Indoorunit display
Judgment Method
Cause of problem
Outdoor unit display
Yes
Did the outdoor Cond Out
sensor connector break away from
the PCB?
Did the resistance
value significantly stray from the following
temperature table?
After separating the outdoor
Cond Out
sensor connector from the PCB, measure the resistance
value between the two terminals.
Restart operation after replace the PCB
Restart operation after connecting
the connector to the
PCB.
Replace this part as it is the defective of the
outdoor Cond Out sensor itself.
Yes
No
No
TemperatureC)
70
60
50
40
30
20
10
0
-10
Resistance (K)
2.2
3.0
4.2
5.8
8.3
12.1
18.0
27.3
43.0
Resistance value measure part
COND
COND

Table of Contents