EasyManua.ls Logo

Samsung AM036 - : Prohibition of the operation of Compressor due to Ooutdoor Temperature

Samsung AM036
344 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Troubleshooting
Samsung Electronics 4-101
4-4-62
,
:
Prohibition of the operation of Compressor due to Ooutdoor Temperature
Indoor unit display
Cause of problem
No sign
t0QFSBUJPO1SPIJCJUJPONPEFCZUIFJOEPPSUFNQFSBUVSFMJNJU
Criteria
:
Right before an outdoor unit starts heating operation by On signal of an indoor Remocon, the
error occurs and prohibits the operation in outdoor temperature over 30°C
:
Right before operating heat refrigerant filling mode by the K1 switch of an outdoor PCB, the error
occurs and prohibits the operation in outdoor temperature over 15°C
Outdoor unit display
1. How to check
The above error code is not caused by a product's problem but a function to protect the product by limiting the available tempera-
ture range
so please refer to the usable temperature range in the product manual.
If the error code is displayed despite a condition that does not belong to any of the above diagnosis m
ethods, read the temperature
sensor value of the outdoor inlet air with View Mode or S-net, and if the actual outdoor temperature is different, please replace the
temperature sensor.
(prohibit heating operation in outdoor temperature over 30°C)
(prohibit heat filling operation in outdoor temperature over 15°C)

Table of Contents

Related product manuals