Refrigerant pipe installation
Selecting the insulation of refrigerant pipe
Insulate the gas pipe and liquid pipe by referring to the thickness of insulator for each pipe size.
The standard condition is 3C(86°F), with humidity less than 85%. In the conditions of high humidity, use one grade
thicker.
Pipe Pipe size [mm (inch)]
Insulation(Cooling, Heating)
Remarks
Standard
[30°C (8F),
Below 85%]
High humidity
[30 °C (86°F),
85% or more]
EPDM,NBR
Liquid pipe
Ø6.35 ~ Ø9.52 (1/4 ~ 3/8) 9t
Heat resisting
temperature is more
than 120°C (248°F)
Ø12.70 ~ Ø50.80 (1/2 ~ 2) 13t
Gas pipe
Ø6.35 (1/4) 13t 19t
Ø9.52 (3/8)
19t 25t
Ø12.70 (1/2)
Ø15.88 (5/8)
Ø19.05 (3/4)
Ø22.23 (7/8)
Insulating refrigerant pipe
You must insulate refrigerant pipe, Y-joint, header joint, and pipe connection area.
If you insulate the pipes, the condensed water does not fall from the pipes.
Check if there are any insulation cracks on the bent pipe.
Insulation
Install the insulation to be
overlapped
Fix securely without any gap.
Indoor unit
Insulation
Gas side pipe
Liquid side pipe
Indoor
unit
Clamp
Pipe insulation Pipe insulation after insulating EEV kit
The insulation of the gas and liquid pipes can be in
contact with each other but they should not press
excessively against each other.
When contacting the gas side and liquid side pipe, use
thicker insulation.
When installing the gas side and liquid side pipes, leave
10mm (3/8inch) of space.
When contacting the gas side and liquid side pipe, use
thicker insulation.
Insulation
Gas pipe
Liquid pipe
Insulation
Gas pipe
10mm (3/8”)
Liquid pipe
10mm (3/8”) 10mm (3/8”)