8
Installation location
Make a space for ventilation and service as seen in the picture.
When multiple outdoor units are combined for installation, allow enough space for ventilation against a wall.
If the ventilation space is not allowed, product malfunction may occur.
The side with logo is the front side of the outdoor unit.
Figure Description
Top view Side view
Back side : Air intake
Front side : Air outlet
Front side :
Air outlet
Back side :
Air intake
• , Air flow direction.
When installing 1 outdoor unit
Unit: mm (inch)
When the air outlet is opposite the wall When the air outlet is toward the wall
300 (12) or more
1500 (60) or
more
When 3 sides of the outdoor unit are blocked by the wall The upper part of the outdoor unit is blocked and the air
outlet is toward the wall
300 (12) or
more
150 (6) or more
600 (24) or more
1500 (60) or
more
2000 (80) or
more
The upper part of the outdoor unit is blocked and the air
outlet is opposite the wall
When the walls are blocking front and the rear of the
outdoor unit
500 (20) or
more
300 (12) or more
1500 (60) or
more
300 (12) or
more
AM0@@FXMDCH_IM_EN_03408A(1).indd 8 2013-03-04 오후 4:28:14