Outdoor unit type
Shape
Model Cooling and Heating 1phase
AM036FXMDCH
AM048FXMDCH
AM053FXMDCH
Installation combination
You must install the indoor unit that uses R410A only.
If sum capacity of the combined indoor units exceeds the capacity of an outdoor unit, the capacity of each indoor unit is
reduced below the rated capacity. Therefore, keeping the combination of indoor units within the capacity of an outdoor
unit is recommended.
Outdoor unit
Outdoor unit capacity
[HP(Ton)]
The maximum number of
connectable indoor units
Total capacity of the
connected indoor units
[kW(MBH)]
AM036FXMDCH 4(3) 6 5.6~14.5(19~ 49)
AM048FXMDCH 5(4) 8 7.0~18.2(24~62)
AM053FXMDCH 6(5) 9 7.8~20.2(27~69)
AM0@@FXMDCH_IM_EN_03408A(1).indd 5 2013-03-04 오후 4:28:13