K13, K14: Changing current limit option table
Switch Function
K13 K14 3 ton 4 ton 5 ton
ON ON Default Default Default
ON OFF Maximum current - 4(A) Maximum current - 2(A) Maximum current - 2(A)
OFF ON Maximum current - 6(A) Maximum current - 4(A) Maximum current - 4(A)
OFF OFF Maximum current - 8(A) Maximum current - 6(A) Maximum current - 6(A)
Classification Model Maximum current
3Ton AM036FXMDCH 22A
4Ton AM048FXMDCH 24A
5Ton AM053FXMDCH 32A
K15, K16: Changing defrost option table
Switch
Function
K15 K16
ON ON MID
ON OFF MID
OFF ON LOW1
OFF OFF LOW2
Defrost mode will start when the temperature difference between outdoor and outdoor heat exchanger has become
more than certain standard.
Factory default status is MID. When the function changes to LOW with option control, defrost entering temperature
decreases. When defrost entering temperature decreases, the operation hour will be long but this means that the
operation hour with the reduced heating capacity increases. This option is used at places where humidity is high and the
defrost mode enters too frequently.
Maintaining factory default status is recommended.