Installation options for the 02 series (detailed)
Option No. for an indoor unit address: 02XXXX-1XXXXX-2XXXXX-3XXXXX
Option SEG1 SEG2 SEG3 SEG4 SEG5 SEG6
Function Page Mode -
Use of external temperature sensor /
Minimizing fan operation when thermostat
is off
Use of central control
Compensation of the
fan RPM
Indication and
details
Indication Details Indication Details - Indication
Details
Indication Details Indication Details
Use of
external
temperature
sensor
Minimizing fan
operation when
thermostat is off
0 2 -
0 Disuse
(Cooling, Heating)
Disuse
0 Disuse 0
Disuse
(recessed
installation)
1 Use
(Cooling, Heating)
Disuse
2 Disuse (Heating) Use (*2)
1 Use
1
High-ceiling
mode (recessed
installation)
3 Use (Heating) Use (*2)
4 Disuse (Cooling) Use
4
Disuse
(exposed
installation)
5 Use (Cooling) Use
6 Disuse
(Cooling, Heating)
Use (*2)
5
High-ceiling
mode (exposed
installation)
7 Use
(Cooling, Heating)
Use (*2)
Option SEG7 SEG8 SEG9 SEG10 SEG11 SEG12
Function Page Use of drain pump
Use of hot water
heater
-
EEV step when
heating stops
-
Indication and
detail
Indication Details Indication Details Indication
Details
-
Indication
Details
-
1
0 Disuse 0
Disuse
0 Default
1 Use 1
Use (*3)
1
Noise
decreasing
setting
2
Use with
3 minute
delay
2
-
3
Use (*3)

Table of Contents