Product Specifications
32 Samsung Electronics
Model
AM045ANLDKH/EU AM056ANLDKH/EU AM071ANLDKH/EU
Power Supply ø, #, V, Hz 1,220~240,50/60 1,220~240,50/60 1,220~240,50/60
Mode
-
HP HP HP
Performance
Capacity
(Nominal)
Cooling
2)
kW 4.5 5.6 7.1
Btu/h 15,400 19,100 24,200
Heating
2)
kW 5 6.3 8
Btu/h 17,000 21,400 27,200
Condensate
(with high fan speed)
Liter/h
Power
Input W 51 73 82
Running Current A 46 68 77
Sound Level Sound Pressure *4) dB(A) 38 42 42
Fan
Type - Sirocco Fan Sirocco Fan Sirocco Fan
Motor
Model - DB31-00671A DB31-00671A DB31-00671B
Type - BLDC Feedback BLDC Feedback BLDC Feedback
Output W 84 84 84
Airflow Rate
Cooling (High) m3/min 11 13.3 16.2
Heating (High)
m3/min 12.8 15.3 18.8
Refrigerant
Type - R410A R410A R410A
Control Method - EDM EEV3.2C Sanhua EDM EEV3.2C Sanhua EDM EEV3.2C Sanhua
Temperature Control - Micom&Thermistors Micom&Thermistors Micom&Thermistors
Safety Devices - Fuse:3.15A/1.6A Fuse:3.15A/1.6A Fuse:3.15A/1.6A
Piping
Connections
Liquid (Flare) ø, mm 6.35 6.35 9.52
Gas (Flare) ø, mm 12.7 12.7 15.88
Drain ø, mm VP25 (OD 32,ID 25) VP25 (OD 32,ID 25) VP25 (OD 32,ID 25)
Weight
Net Weight kg
18.8 18.8 22.0
Shipping Weight kg 21.8 21.8 25.6
Dimensions
Net Dimensions
(W x H x D)
mm 900*199*440 900*199*440 1100*199*440
Shipping Dimensions
(W x H x D)
mm 1151*280*544 1151*280*544 1351*280*544
Functions
Auto Restart - O O O
Auto Swing - X X X
Group/Individual Control - O O O
External Contact Control - O O O
Trouble Shooting by LED - X X X
Standard
Accessories
Installation Manual - O O O
Operation Manual - O O O
Pattern Sheet for Installation - X X X
Flexible Drain Hose - O O O
Filter / Safety Grille - Filter(Washable) Filter(Washable) Filter(Washable)
Optional
Accessories
Wireless Remote Controller - MR-DH00 MR-DH00 MR-DH00
Duct Receiver
Kits
Receiver - MRK-A10 MRK-A10 MRK-A10
Receiver Wire
- MRW-10A MRW-10A MRW-10A
Wired Remote
Controller
Simplied
- MWR-WE10N MWR-WE10N MWR-WE10N
External Contact Interface Module - MIM-B14 MIM-B14 MIM-B14
*1) Mode
- HP : Heat Pump, HR : Heat Recovery
*2) Nominal cooling capacities are based on;
- Indoor temperature : 27˚C DB, 19˚C WB
- Outdoor temperature : 35˚C DB, 24˚C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m
*3) Nominal heating capacities are based on;
- Indoor temperature : 20˚C DB, 15˚C WB
- Outdoor temperature : 7˚C DB, 6˚C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m
*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.
*5) Specifications may be subject to change without prior notice for product improvement.