Troubleshooting
Samsung Electronics 369
■
Forced defrost operation
► Forced defrost operation : Is operation when Frost Formation occurs in the outdoor. (When carried out the service)
■
Forced oil recovery operation
► Forced oil recovery operation : Oil recovery in the outdoor unit for the purpose of moving, installation if necessary.
Method of Entry K2 Tact Switch 6 times
Start pattern Heating commissioning pattern
Defrost start Defrost start : It is after 10 minutes which Safety Start finishes.
Defrost off General defrost operation conditions are the same as.
Etc. Defrost shut down and stop the normal pattern of the outdoor unit stop.
Method of Entry K2 Tact Switch 7 times
Start pattern Outdoor temperature is more than 10°C : Cooling commissioning
Outdoor temperature is less than 10°C : Heating commissioning
Oil recovery start Oil recovery start : It is after 10 minutes which Safety Start finishes.
Etc. Oil recovery shut down and stop the normal pattern of the outdoor unit stop.
4-2-2 DVM S Models EEPROM Code Table
No. Model Name EEP Code
1 AM080FXVAGH/EU DB82-01358A
2 AM100FXVAGH/EU DB82-01359A
3 AM120FXVAGH/EU DB82-01360A
4 AM140FXVAGH/EU DB82-01361A
5 AM160FXVAGH/EU DB82-01362A
6 AM180FXVAGH/EU DB82-01363A
7 AM200FXVAGH/EU DB82-01364A
8 AM220FXVAGH/EU DB82-01365A
9 AM080FXVAGR/EU DB82-01330A
10 AM100FXVAGR/EU DB82-01331A
11 AM120FXVAGR/EU DB82-01332A
12 AM140FXVAGR/EU DB82-01333A
13 AM160FXVAGR/EU DB82-01334A
14 AM180FXVAGR/EU DB82-01335A
15 AM200FXVAGR/EU DB82-01336A
16 AM220FXVAGR/EU DB82-01337A
17 AM080FXMDGH/EU DB82-01774A
18 AM090FXMDGH/EU DB82-01776A