Product Specifications
92 Samsung Electronics
Indoor Unit (cont.)
Model AM140JNEPEH/EU AM220JNEPEH/EU AM280JNEPEH/EU
Power Supply Φ, #, V, Hz 1,2,220-240,50 1,2,220-240,50 1,2,220-240,50
Mode
*1)
HP HP HP
Performance
Capacity
Cooling
*2)
kW 14.0 28.0 28.0
Btu/h - - -
Heating
*3)
kW 8.9 17.4 17.4
Btu/h - - -
Condensate (with High fan speed) Liters/h
Power
Input W 220 300 370
Running Current A 1.6 2.2 3.0
Sound Level Sound Pressure (High/Low)
*4)
dB(A) 48 52 56
Fan
Type - Sirocco Fan Sirocco Fan Sirocco Fan
Motor
Model -
Type - BLDC BLDC BLDC
Output
W
Airflow Rate
H/M/L m3/min 18 28 50
External Pressure Min/Std/Max
mmAq
20 25 30
Refrigerant
Type - R410A R410A R410A
Control Method
-
EEV EEV EEV
Temperature Control - Micom&Thermistors Micom&Thermistors Micom&Thermistors
Safety Devices - Fuse Fuse Fuse
Piping
Connections
Liquid (Flare) ø, mm 9.52 9.52 9.52
Gas (Flare) ø, mm 15.88 22.22 22.22
Drain ø, mm VP25 (OD 32,ID 25) VP25 (OD 32,ID 25) VP25 (OD 32,ID 25)
Weight
Net Weight kg 51 85 85
Shipping Weight kg 61 95 95
Dimensions
Net Dimensions (W x H x D)
mm
1110x390x650 1240x470x1040 1240x470x1040
Shipping Dimensions (W x H x D)
mm
1335x512x829 1507x558x1155 1507x558x1155
Functions
Auto Restart
-
O O O
Auto Swing
-
X X X
Group/Individual Control - O O O
External Contact Control - O O O
Trouble Shooting by LED - O O O
Standard
Accessories
Installation Manual - O O O
Operation Manual - O O O
Pattern Sheet for Installation - O O O
Flexible Drain Hose - X X X
Filter / Safety Grille - X X X
Optional
Accessories
Wireless Remote Controller -
DMS 2.0 - MIM-D00AN MIM-D00AN MIM-D00AN
Wired Remote
Controller
Simplified - MWR-WE10N MWR-WE10N MWR-WE10N
EHS MWR-WW00N MWR-WW00N MWR-WW00N
External Contact Interface Module - MIM-B14 MIM-B14 MIM-B14
Drain Pump MDP-N047SNC0D ADP-N047SNC1D ADP-N047SNC1D
*1) Mode
- HP : Heat Pump, HR : Heat Recovery
*2) Nominal cooling capacities are based on;
- Indoor temperature : 27˚C DB, 19˚C WB
- Outdoor temperature : 35˚C DB, 24˚C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m
*3) Nominal heating capacities are based on;
- Indoor temperature : 20˚C DB, 15˚C WB
- Outdoor temperature : 7˚C DB, 6˚C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m
*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.