Product Specifications
68 Samsung Electronics
1) Nominal heating capacities are based on;
- Indoor temperature : 20˚C DB, 15˚C WB
- Outdoor temperature : 7˚C DB, 6˚C WB, Rated flow standard : Temperature of the Outlet water 65℃
2) Rated heating capacity : Outdoor temperature 7˚C standard and outdoor temperature falls below zero, heating capacity can drop, depending
on the temperature condition.
3) Equivalent refrigerant piping : 7.5m, Level differences : 0m
Type
(Hydro Unit HT)
Model AM160TNBFEB/EU AM250TNBFEB/EU AM160TNBFGB/EU AM250TNBFGB/EU
Division Heating Heating Heating Heating
Power Supply 1ø, 220-240V, 50Hz 1ø, 220-240V, 50Hz 3ø, 380-415V, 50Hz 3ø, 380-415V, 50Hz
Performance
Horse Power HP 5 8 5 8
Heating
kW 16.0 25.0 16.0 25.0
Kcal/h 13760 21500 13760 21500
Power
Running Current A 14.3 23.1 4.85 7.85
Input W 3,100 5,000 3,100 5,000
Refrigerant
Type - R-134a R-134a R-134a R-134a
Charging kg 2.15 2.15 2.15 2.15
Piping
(Refrigerant)
Liquid ø,mm 9.52 9.52 9.52 9.52
Gas ø,mm 15.88 15.88 15.88 15.88
Piping(Water)
Inlet/Outlet A(Inch) 25A(PT1) 25A(PT1) 25A(PT1) 25A(PT1)
Max. Hydraulic Mpa 1.0 1.0 1.0 1.0
Rated flow rate(Water Piping) LPM 23 36 23 36
Set Size
Net Weight kg 105.0 105.0 103.5 103.5
Shipping Weight kg 112.5 112.5 111.0 111.0
Net Dimension(WxHxD) mm 518 x 1,210 x 330 518 x 1,210 x 330 518 x 1,210 x 330 518 x 1,210 x 330
Shippingt Dimension(WxHxD mm 652 x 1,374 x 426 652 x 1,374 x 426 652 x 1,374 x 426 652 x 1,374 x 426
■ Hydro unit HT (cont.)
Indoor Unit (cont.)