Piping Diagram
Samsung Electronics 324
Solenoid Valve EVI, Solenoid Valve - EVI Bypass
Solenoid Valve - Hot Gas Bypass
Solenoid Valve - Hot Gas Bypass 2
Purpose
Switch between EVI Bypass Mode, EVI On Mode, and EVI Off Mode, depending on the EVI EEV status.
Concept
- Solenoid valve – EVI : When Vapor/Flash Injection is in use, the valve is closed to let refrigerant flow into the compressor.
- Solenoid valve - EVI Bypass : If a compressor has stopped, the valve is closed to prevent the refrigerant that has passed through
the EVIEEV from flowing into the compressor.
Control specifications in detail
Control valves according to the EVI Mode, as shown below.
Purpose
Protect the system when high pressure is abnormally high or low pressure is abnormally low.
Concept
If either pressure is abnormal, the valve is opened to bypass the high-pressure gas to the low pressure pipe.
This will change the pressure.
Control specifications in detail
ON if high pressure is above 39.5kgf/cm2,g / OFF if below 38.5kgf/cm2,g
ON if cooling low pressure is below 3.2kgf/cm2,g / OFF if above 4.2kgf/cm2,g (at minimum frequency, OFF if above 6.0kgf/cm2,g)
ON if cooling low pressure is below 0.9kgf/cm2,g / OFF if above 1.7kgf/cm2,g
Purpose
Prevent refrigerant from stagnating in the high pressure gas pipe in cooling-only mode.
Concept
- In cooling-only mode, the valve is opened to switch the high pressure gas pipe to the low pressure gas pipe.
- If the valve is closed, refrigerant stagnates in the high pressure gas pipe causing a lack of refrigerant.
- HR Only
Control specifications in detail
If using the Heat Recovery device, the valve is opened (ON) after cooling-only mode has been on for more than 20 minutes or when
cooling oil return mode is active.
EVI Mode
Electronic Expansion Valve
- EVI
Solenoid valve
- EVI
Solenoid valve
- EVI Bypass
* Condition
EVI Bypass mode Open Open Open Normal Operation
EVI On mode Open Open Close
- All comp. in unit 70hz
- Ambient Temp. < 36 (cool)
< 10 (heat)
- Control by unit
EVI Off mode Close Open Open
- Safety start
- Defrost
7-3 Functions (cont.)
7-3-2-1 Actuator (cont.)
7-3-2 Control (cont.)