Piping Diagram
Samsung Electronics 344
Oil return operation
Purpose
Perform oil return after a specified amount of time has elapsed in order to prevent an insufficient amount of oil in compressors.
Concept
The compressor capacity is raised to increase the amount of refrigerant circulation. This will return oil remaining in indoor units
and piping.
Control specifications in detail
- Oil recovery operation shall be performed to prevent a compressor from being short of oil. Oil in pipes or indoor unit will be col-
lected to outdoor unit by starting oil collecting operation.
- Oil collecting operation will begin 7 hours after outdoor unit starts to operate but time might be reduced depending on the
operating condition (# of compressor in operation and operating frequency). Once defrosting operation operate for more than
3 minutes during heating operation, it will be considered to have done oil collecting operation.
- Master outdoor unit will be changed after oil collecting operation.
Actuator Oil return Operation
Capacity of compressor Current capacity + additional capacity
Outdoor EEV Normal control
Outdoor Fan Normal control
Indoor EEV
Operating indoor units Higher step of [400(C)/300(H) or Current step]
Stopped indoor units 400(C)/300(H)
Indoor Fan Normal control
Time 3min(C) / 6min(H)
*Additional capacity = Compensation capacity of stop units
* EEV step can be varied by cycle condition.
7-3 Functions (cont.)
7-3-2-4 Special operation modes (cont.)
7-3-2 Control (cont.)