Samsung Electronics 42
Product Specifications
Image
Model Name AM240HXVAGH AM260HXVAGH
Power Supply Φ, V, Hz 3/AC380~415/50 3/AC380~415/50
Mode - HEAT PUMP HEAT PUMP
Performance
HP HP 24 26
Capacity
(Nominal)
Cooling
kW 67.2 72.8
Btu/h 57,800 62600
Heating
kW 75.6 81.9
Btu/h 65,000 70,400
Power
Power Input
(Nominal)
Cooling 1)
kW
17.10 19.30
Heating 2) 19.80 21.80
Current Input
(Nominal)
Cooling 1)
A
26.83 30.28
Heating 2) 31.06 34.20
Running Current
Cooling
A
26.83 30.28
Heating 31.06 34.20
Max 55.00 58.00
Power Consumption
Cooling 1)
kW
26.83 30.28
Heating 2) 31.06 34.20
MCA(Minimum Circuit Amps)
A
60.50 63.80
MFA/MOP(Maximum Fuse Amps) 75.00 75.00
COP
Nominal Cooling 1)
W/W
3.930 3.772
Nominal Heating 2) 3.818 3.757
ESEER - -
Compressor
Type - INV x 2EA INV x 2EA
Output kW - -
Model Name - DS-GB066FA* DS-GB070FA*
Oil
Type - FVC68D FVC68D
Initial Charge cc 6200 6200
Fan
Type - Propeller + BLDC Propeller + BLDC
Output x n W 620 x 2 620 x 2
Air Flow Rate
/min 310 310
l/s 5167 5167
External Static
Pressure
Max.
mmAq - -
Pa - -
Piping
Connection
Liquid Pipe
Type Braze connection Braze connection
Φ, mm 15.88 19.05
Φ, inch 5/8" 3/4"
Gas Pipe
Type Braze connection Braze connection
Φ, mm 34.92 34.92
Φ, inch 1+3/8" 1+3/8"
Discharge Gas Pipe
Φ, mm - -
Φ, inch - -
Piping length
ODU-IDU Max. m 200(220) 200(220)
After branch Max. m 90 90
Total piping length System Actual m 1000 1000
Level difference
ODU-IDU
Outdoor unit in high-
est position
m 110 110
Indoor unit in highest
position
m 110 110
IDU-IDU Max. m 50 50
Refrigerant
Type - R410A R410A
Factory Charging kg 14.3 14.3
Sound
Sound Pressure
Cooling
dB(A)
- -
Heating - -
Sound Power - -
External
Dimension
Net Weight
DVMS HP
kg
360 360
DVMS HR 370 370
Shipping Weight
DVMS HP
kg
1,295 x 1,695 x 765 1,295 x 1,695 x 765
DVMS HR 1,363 x 1,887 x 832 1,363 x 1,887 x 832
Net Dimension (WxHxD) mm -5.0 ~ 48.0 -5.0 ~ 48.0
Shipping Dimension (WxHxD) mm -20.0 ~ 24.0 -20.0 ~ 24.0
Operating
Temp. Range
Cooling
DVMS HP
-5.0 ~ 48.0 -5.0 ~ 48.0
DVMS HR -15.0 ~ 48.0 -15.0 ~ 48.0
Heating
-25.0 ~ 24.0 -25.0 ~ 24.0
2-5-1 Outdoor Unit (cont.)
2-5 Product Specification (cont.)
1) Nominal cooling capacities are based on;
- Indoor temperature : 27°C DB, 19°C WB
- Outdoor temperature : 35°C DB, 24°C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m
2) Nominal heating capacities are based on;
- Indoor temperature : 20°C DB, 15°C WB
- Outdoor temperature : 7°C DB, 6°C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m
3) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50~130%.
4) Sound power level is an absolute value that a sound source generates.
Sound pressure level is a relative value, depending on the distance and acoustic environment.
Sound values are obtained in an anechoic room.
Sound values of multi combination are theoretical values based on sound results of individual installed units.
5) These products contain R410A which is fluorinated greenhouse gas.
6) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether the PDM kit should be installed or not.)
*PDM kit: Pressure Drop Modulation kit. When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local dealer for more information.
In case you want to know more information regarding capacity and correction, please refer to capacity table TDB on pvi.samsung.com site.