Troubleshooting
316 Samsung Electronics
70
60
50
40
30
20
10
0
-10
2.2
3.0
4.2
5.8
8.3
12.1
18.0
27.3
43.0
Did the connector for Water Out Temperature
Sensor breakaway from the PCB?
Restart operation after connecting the
connector to PCB.
Yes
No
Yes
No
Temperature(℃)
Resistance(KΩ)
Resistance value
measure part
Separate the connector of Water Out
Temperature Sensor from the PCB and
measure the resistance value between
the 2 terminals.
Did the resistance value significantly
stray from the following temperature table?
Restart operation after replace the PCB .
Replace this part as it is the defective of
Water Out Temperature Sensor itself.
4-4-91
Hydro Unit Water Out Temperature Sensor Error (Open/Short)
Indoor unit display
Cause of problem
tHydro Unit Water Out Temperature Sensor Open/Short error of xxx
Criteria
tRefer to the judgment method below.
Outdoor unit display
↔ XXX (xxx : Address of Indoor Unit that err or occurred))
1. Inspection Method