Troubleshooting
5-3-9
Check
of
instantaneous
over-current
protection
of
IPM
circuit.
>
Inverter
instantaneous
over-current
protection
mode
is
the
mode
to
be
actuated
in
order
to
prevent
the
damage
of
elements
from
the
peak
current
of
IPM
circuit
elements.
>
In
case that
the
inverter
circuit
instantaneous
over-current
protection
mode
actuates,
check
the
following
items.
(Condition
of
installation)
The
ventilation
is
not
good
because
the
outdoor
unit
is
installed
wrong
(the
ambient
tempera-
ture
is
higher
than
50
(°C)
)
Reinstall
the
outdoor
unit
so
that
the
good
ventilation
can
be
made.
¢In
case
that
the
operation
is
made
with
the
cover
bent
of
the
outdoor
unit.
Take
out
the
cover.
¢If
two
outdoor
units
are
operating
face
to
face,
(the
bad
ventilation
is
made)
Reinstall
the
outdoor
unit
for
the
good
ventilation.
¢The
air
circulation
is
bad due
to
the
attachment
of
falling
leaves.
~—
Take
away
the
leaves
for
the
good
ventilation.
elf
the
Refrigerant
is
overcharged.
Check
the
amount
of
Refrigerant.
(Unit
defect)
¢If
the
comp
is
locked.
Replace
the
comp.
¢lf
the
comp
is
operating
without
the
revolution
of
fan
motor.
Check
the
fan
motor
connector
and
replace
the
fan
motor.
¢In
case
the
parts
of
the
control
board
is
damaged.
Replace
simultaneously
the
inverter
control
board.
5-3-10
Check
of
the
comp
discharge
gas
temperature
and
OLP
temperature
abnormal
rise.
>
If
the
comp
discharge
gas
temperature
and
OLP
temperature
rises
higher
than
a
certain
level,
it
protects
the
circuit.
>
If
the
comp
discharge
gas
temperature
and
OLP
temperature
rises
abnormally,
check
the
following
items.
(Condition
of
installation)
The
ventilation
is
not
good
because
the
outdoor
unit
is
installed
wrong
(the
ambient
tempera-
ture
is
higher
than
50
(°C)
)
:
Reinstall
the
outdoor
unit
so
that
the
good
ventilation
can
be
made.
-
@In
case
that
the
operation
is
made
with
the
cover
bent
of
the
outdoor
unit.
Take
out
the
cover.
¢If
two
outdoor
units
are
operating
face
to
face,
(the
bad
ventilation
is
made)
Reinstall
the
outdoor
unit
for
the
good
ventilation.
¢The
air
circulation
is
bad due
to
the
attachment
of
falling
leaves
Take
away
the
leaves
for
the
good
ventilation.
elf
the
refrigerant
is
insufficient.
Fill
up
the
amount
of
refrigerant.
(Unit
defect)
¢If
the
comp
is
locked.
Replace
the
comp.
¢If
the
comp
is
operating
without
the
revolution
of
fan
motor
Take
out
the
protection
cover.
Check
the
fan
motor
connector
and
replace
the
fan
motor.
5-8
Samsung
Electronics