2-2 Samsung Electronics
2-2 Product Specifications
Model
Item
AQV09NSA/AQV09FC AQV12NSA/AQV12FC
Indoor Unit Outdoor Unit Indoor Unit Outdoor Unit
Type Wall-mounted Wall-mounted
Performance
Capacity
Cooling
kW
(Low / Std / Max)
0.99 / 2.50 / 3.20 0.99 / 3.30 / 3.80
Heating 1.20 / 3.30 / 4.20 1.40 / 4.00 / 4.70
Running Frequency
Cooling
Hz
(Low / Std / Max)
20 / 52 / 70 25 / 69 / 79
Heating 25 / 64 / 75 30 / 76 / 88
Dehumidifying ℓ/h 1.3 1.6
Air Volume
Cooling
/min
(H/M/L)
7.2/5.8/4.0 30 8.5/6.9/5.2 30
Heating 7.8/6.6/4.6 29 9.2/7.5/6.0 29
Noise
Cooling
dB
(H/L)
43 / 25 53 43 / 25 53
Heating 43 / 25 53 43 / 25 53
Energy Efficiency Ratio
Cooling
W/W
(Std)
3.40 3.21
Heating 3.63 3.61
Power ph-V-Hz 1-220/240-50 1-220/240-50
Power
Power Consumtion
Cooling
W
(Low / Std / Max)
270 / 735 / 980 320 / 1028 / 1210
Heating 300 / 910 / 1100 350 / 1108 / 1400
Operating Current
Cooling
A
(Low / Std / Max)
1.6 / 3.5 / 4.5 1.9 / 4.9 / 5.5
Heating 1.7 / 4.4 / 5.2 2.2 / 5.2 / 6.2
Power Factor
Cooling
%
(Low / Std / Max)
70 / 85 / 90 70 / 90 / 90
Heating 70 / 85 / 90 70 / 90 / 90
Power Cord
Length m 2 2
Number of Core Wire
3 3
Capacity
A 10 10
Size
Outer Dimension
W x H x D
mm 825x285x189 720x548x265 825x285x189 720x548x265
Weight (Net) kg 7.8 31.5 9.4 31.5
Refrigerant Pipe
Liquid mm x L(m) Φ6.35 x 5 Φ6.35 x 5
Gas mm x L(m) Φ9.52 x 5 Φ9.52 x 5
Drain Hose D x L(mm) Φ18 x 550 Φ18 x 550
Compressor
Type Rotary, G4C090LUDER Rotary, G4C090LUDER
Motor
Type Hermetic Hermetic
Rated Output 853W 853W
Oil Type FREO68ES-T FREO68ES-T
Blower
Type Cross-flow Propeller Cross-flow Propeller
Motor
Type Resin / Steel Resin / Steel Resin / Steel Resin / Steel
Rated Output
W 27 50 27 50
Heat Exchanger 2 Row 10 Step 1 Row 20 Step 2 Row 10 Step 1 Row 20 Step
Refrigerant Control Unit Check Valve, Capillary Check Valve, Capillary
Freezer Oil Capacity cc 320 320
Refrigerant to Change (R410A)
g 800 850
Protection Device (OLP) None None
Cooling Test Condition Indoor Unit : DB27
°C
WB 19
°C
Outdoor Unit : DB35
°C
WB 24
°C
Heating Test Condition Indoor Unit : DB20
°C
WB 15
°C
Outdoor Unit : DB7
°C
WB 6
°C
Operation conditon range
cooling
indoor 16
°C
~ 32
°C
16
°C
~ 32
°C
Outdoor -10
°C
~ 43
°C
-10
°C
~ 43
°C
heating
indoor 27
°C
or less 27
°C
or less
Outdoor -15
°C
~ 24
°C
-15
°C
~ 24
°C