In case you want more information about the controllers and accessories, please refer to the Controller and Accessory TDB
on pvi.Samsung.com site or Global Partner Portal site.
13. Installation
Important information regulation regarding the
refrigerant used

not vent gases into the atmosphere.
CAUTION
Inform user if system contains 5 tCO
2
e or more of

be checked for leakage at least once every 12 months,
according to regulation n°517/2014. This activity has

In case situation above (5 tCO
2
e or more of
R-32), installer (or recognized person which has

maintenance book, with all the information recorded
according to REGULATION (EU) No 517/2014 OF THE
EUROPEAN PARLIAMENT AND OF THE COUNCIL of

Please ll in the following with indelible ink on the
refrigerant charge label supplied with this product and
on this manual.
: The factory refrigerant charge of the product.

+ : The total refrigerant charge.
Indoor Unit
Outdoor Unit
1
GWP = 675
Unit kg tCO
2
e
, a
, b
+ , c
Refrigerant type GWP value
R-32 675
GWP: Global Warming Potential
Calculating tCO
2
e : kg x GWP / 1000
NOTE
a
Factory refrigerant charge of the product: see unit name plate
b

to the above information for the quantity of refrigerant
replenishment.)
c
Total refrigerant charge
d
Refrigerant cylinder and manifold for charging
LEAK TEST WITH NITROGEN (before opening valves)
In order to detect basic refrigerant leaks, before
recreating the vacuum and recirculating the R-32, it is
the responsibility of the installer to pressurize the whole
system with nitrogen (using a cylinder with pressure
reducer) at a pressure above 4 MPa (gauge).
LEAK TEST WITH R-32 (after opening valves)
Before opening valves, discharge all the nitrogen into
the system and create vacuum. After opening valves
check leaks using a leak detector for refrigerant R-32.
Once you have completed all the connections, check for

for HFC refrigerants.