4-36 4-37
Troubleshooting
- Operation Error
Contents
Q1 
Check point Remarks
Analysis
This problem is caused by user’s fault. User’s simultaneously operate 2 more indoor units in the same time cool-
ing and heating mode.
Guidance
FJM is operate by just cooling or heating mode only. (Only, HR system can operate cooling and heating mode
simultaneously in the same time)

Contents
Q2 
Check point Remarks
Analysis
E416 is outdoor unit high discharge temperature safety control Error code.
After System restart automatically until 3 times, system stop and display this error.
System can be operated by remote controller signal and K3(reset) key input.
Step 1
Check outdoor units installation environment.

Step 2 Check refrigerant leakage.
Step 3 Check outdoor EEV operation.
Contents
Q3 
Check point Remarks
Analysis
E458 Error is related with outdoor unit fan Error.
Especially, If system have a some problem in fan, in heating mode , it will be happened.
And In auto address setting, without pipe checking operation must be happened it.
Step 1 Check to outdoor fan operation.
Step 2 If outdoor fan operation is clear, start to pipe checking operation.
Guidance
-
erant distribution control is malfunction.
It make our system to confuse it’s condition.
But, basically this error code is concerned about fan error.
Contents
Q4 
Check point Remarks
Analysis
This is caused by protection mode behavior.
This is indoor Evaporator Freezing protection mode.
It can also occur intermittently when using 1 or 2 indoor units for cooling at low indoor and outdoor temperatures.
Step 1 Please, check indoor unit, whether inlet or outlet grill is closed.
Step 2 Please, check indoor unit, whether indoor fan is working.
Contents
Q5 
Check point Remarks
Analysis
The product is out of the range of cooling operation.
Please, Remember cooling operation range.