INSTALLING THE
OUTDOOR UNIT
Auxiliary Circuit Breaker
Auxiliary circuit breaker should be installed near outdoor unit so that each
access is possible. Main/outdoor power supply cable are connected to
upper/lower terminal of auxiliary circuit breaker.
It is necessary that the conduit kit for power supply to the outdoor
unit be installed between auxiliary power switch and the outdoor unit.
(the conduit kit is optional)
Outdoor unit
Distribution
board
Auxiliary
power
swich
The designs and shape are subject to
change according to the model.
Electrical Work
When using the special NFB, use the NFB to bear the capacity of the air conditioner.
Otherwise, the shot circuit in the NFB may occur.
The power cable and the assembly cable are not supplied with the air conditioner.
MODEL
AS09A5(6)MAF
Power supply
Power cable
Assembly cable
Operating current(C)
Starting Current
Power consumption (C)
115V/60Hz
Single phase
AS07A5(6)MA
115V/60Hz
Single phase
3G AWG 14
4G AWG 16
43A32A
6.4 8.1
950W680W
AS12AA(B)MCF
208-230V/60Hz
Single phase
31A
5.4
1230W
1 The supply voltage must be the same as the rated voltage of the
air conditioner.
2 Prepare the power souce for exclusive use with the air conditioner.
3 Use 15 amperes time delay fuse or circuit breaker.