SAMSUNG | 31
INSTALLING
5
Installation Diagram of Indoor Unit and Outdoor Unit (Cont.)
5-2-6. Flare Modification
TOOLS USED
FLARE MODIFICATION PROCEDURE
1. Cut the pipe using a pipe cutter.
2. Remove burrs at the tip of the pipe cut.
3. Insert a flare nut into the pipe and modify flare.
Outer diameter A(mm)
ø6.35mm 1.3
ø9.52mm 1.8
ø12.7mm 2.0
90
D
A
Oblique
Roughness
Burr
Pipe
Reamer
* Unproper flaring
Inclined Surface
damaged
Cracked Uneven
thickness
CAUTION
Burrs not removed may result in leakage of gas.