EasyManua.ls Logo

Samsung DVE53BB8900GA3 - Ducting Requirements

Samsung DVE53BB8900GA3
72 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
English
English19
Ducting requirements
Weather hood type
Recommended
Use only for short-run
installation
4” (10.2 cm) 2.5” (6.4 cm)
No. of 90° elbows Rigid Rigid
0 80 ft. (24.4 m) 74 ft. (22.6 m)
1 68 ft. (20.7 m) 62 ft. (18.9 m)
2 57 ft. (17.4 m) 51 ft. (15.5 m)
3 47 ft. (14.3 m) 41 ft. (12.5 m)
NOTE
* Use a 4-inch (10.2 cm) diameter rigid aluminum or galvanized steel duct.
If you integrate the dryers vent system with an existing exhaust system:
Make sure the exhaust system meets all applicable local, state, and national regulations.
Verify you are not using flexible plastic duct.
Make sure to check for and remove all lint buildup from inside the existing ducts.
Confirm the duct is not kinked or crushed.
Make sure the exhaust hood damper opens and closes freely.
Manometer measurements
The static pressure in any exhaust system must not exceed 0.83 inches of water column or be less than 0.
Note that these values are measured with the dryer running with a manometer presented to the exhaust
duct that connects to the dryer. The dryer tumbler must be empty and lint filter clean.
Untitled-11 19 2023-06-28()  2:19:52

Related product manuals