Standard module (Heat recovery)
Model MCA MFA
AM320FXVGNR 67.5 80
AM340FXVGNR 69.5 80
AM360FXVGNR 69.5 80
AM380FXVGNR 76.5 90
AM400FXVGNR 83.6 100
AM420FXVGNR 87.0 100
AM440FXVGNR 98.0 125
AM460FXVGNR 105.0 125
AM480FXVGNR 112.1 125
AM500FXVGNR 115.5 150
AM520FXVGNR 117.5 150
AM540FXVGNR 128.0 150
AM560FXVGNR 133.0 150
AM580FXVGNR 140.0 175
AM600FXVGNR 146.0 175
AM620FXVGNR 140.5 175
AM640FXVGNR 142.5 175
AM660FXVGNR 142.5 175
AM680FXVGNR 149.5 175
AM700FXVGNR 156.6 175
AM720FXVGNR 160.0 200
AM740FXVGNR 162.0 200
AM760FXVGNR 172.5 200
AM780FXVGNR 177.5 200
AM800FXVGNR 184.5 225
AM820FXVGNR 190.5 225
AM840FXVGNR 201.0 225
AM860FXVGNR 206.0 250
AM880FXVGNR 213.0 250
AM900FXVGNR 219.0 250
When installing outdoor units in module, select the power supply cable according to the sum of outdoor unit capacity.
(Refer to the table for each model)
Power Supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed exible
cord. (Code designation IEC:60245 IEC 66 / CENELEC: H07RN-F)
Ex.) AM500XVA✴✴
AM120XVA✴✴ : 4 mm
2
AM280XVA✴✴ : 16 mm
2
AM500XVA✴✴ : 35 mm
2
AM220XVA✴✴ AM160XVA✴✴ AM120XVA✴✴
ELCB
MCCB+ ELB