97
ENGLISH
K4 (Number of
press)
KEY operation
Display on segment
SEG 1 SEG2, 3, 4
25 times Current frequency (Compressor 1) P
120 Hz 1,2,0
26 times Current frequency (Compressor 2) Q
120 Hz 1,2,0
27 times Suction 2 temperature R
-42 °C -, 4, 2
28 times Master indoor unit address S
Master indoor unit not selected BLANK, N, D
If indoor unit No.1 is selected as the master unit 0, 0, 1
K4 (Number of
press)
Press and hold the
K4 to enter the
setting
Displayed content
Display on segment
page1 page2
1 time Main version MAIN Version (ex. 1412)
2 times Hub version HUB Version (ex. 1412)
3 times Inverter 1 version INV1 Version (ex. 1412)
4 times Inverter 2 version INV2 Version (ex. 1412)
5 times Fan 1 version FAN1 Version (ex. 1412)
6 times Fan 2 version FAN2 Version (ex. 1412)
7 times EEP version EEP Version (ex. 1412)
8 times Automatically assigned address of the units AUTO
SEG1 SEG2 SEG3, 4
Indoor unit: “A”
MCU: “C”
Indoor unit: “0”
MCU: “1”
Address
(ex: 07)
9 times Manually assigned address of the units MANU
SEG1 SEG2 SEG3, 4
Indoor unit: “A” Indoor unit: “0”
Address
(ex: 15)