ENGLISH
Environment Installation conditions Anti-Corrosion Eect from Installation Anti corrosion Eect by Maintenance
Seashore
Seashore within 500m
Direct exposure
With Anti-corrosion coating: 2
years from installation
*
Check 1 year later from installation
After Corrosion Protection period
(2 years)
Cleaning & Spray R-Pro :
2 years extended
Seashore within 500m
Building / Protection Wall
With Anti-corrosion coating:
4 years from installation
Without Anti-corrosion
coating: 2 years from
installation
* Check 1 year later from installation
After Corrosion Protection period
Cleaning & Spray R-Pro (With
initial coating):
4 years extended
Cleaning & Spray R-Pro
(without initial coating):
2 years extended
Seashore within 500m~2km
With Anti-corrosion coating: 4
years from installation
Without Anti-corrosion
coating: 2 years from
installation
* Check 1 year later from installation
After Corrosion Protection period
Cleaning & Spray R-Pro (With
initial coating):
4 years extended
Cleaning & Spray R-Pro
(Without initial coating):
2 years extended
Seashore
+
Corrosive gas area
Seashore within 500m
Corrosive gas area
With Anti-corrosion coating: 2
years from installation
* Check 1 year later from installation
After Corrosion Protection period
(2 years)
Cleaning & Spray R-Pro :
2 years extended
Seashore within 500m~2km
Corrosive gas area
Corrosive gas area
The place where corrosive
gas generates