10. Installation
62
Refrigerant pipe installation
Refrigerant pipe installation
Basic amount of refrigerant within the outdoor unit (kg)
- Amount of additional refrigerant has to be calculated based on the sum of all liquid pipe length.
Classification AM080JXVHGH/EU AM100JXVHGH/EU AM120JXVHGH/EU AM140JXVHGH/ET AM160JXVHGH/ET AM180JXVHGH/ET
Basic amount 6.5 6.5 6.5 9.4 9.4 8.4
Classification AM200JXVHGH/ET AM220JXVHGH/ET AM240KXVGGH/ET AM260KXVGGH/ET AM280KXVGGH/ET
Basic amount 11.0 11.0 14.0 14.0 14.0
Classification AM080JXVAGH/EU AM100JXVAGH/EU AM120JXVAGH/EU AM140KXVAGH/ET AM160KXVAGH/ET AM180KXVAGH/ET
Basic amount 5.5 5.5 6.5 7.7 8.4 8.4
Classification AM200KXVAGH/ET AM220KXVAGH/ET AM240KXVAGH/ET AM260KXVAGH/ET AM280KXVAGH/ET AM300KXVAGH/ET
Basic amount 8.4 8.4 14.0 14.0 14.0 14.0
Classification AM100MXVDGH/ET AM120MXVDGH/ET AM140MXVDGH/ET AM160MXVDGH/ET AM180MXVDGH/ET
Basic amount 5.5 6.5 7.7 8.4 8.4
Classification AM080JXVHGR/EU AM100JXVHGR/EU AM120JXVHGR/EU AM140JXVHGR/ET AM160JXVHGR/ET AM180JXVHGR/ET
Basic amount 6.5 6.5 6.5 9.4 9.4 8.4
Classification AM200JXVHGR/ET AM220JXVHGR/ET AM240MXVGNR/ET AM260MXVGNR/ET AM280MXVGNR/ET AM300MXVANR/ET
Basic amount 11.0 11.0 14.0 14.0 14.0 14.0
Amount of additional refrigerant depending on the pipe size (ⓐ)
- Amount of additional refrigerant has to be calculated based on the sum of all liquid pipe length.
Size of liquid pipe Ø 6.35 Ø 9.52 Ø 12.70 Ø 15.88 Ø 19.05 Ø 22.22 Ø 25.40 Ø 28.58
Additional amount (kg/m) 0.02 0.06 0.125 0.18 0.27 0.35 0.53 0.65
- For the indoor unit already connected to EEV kit, the additional refrigerant charging is 0.01kg per meter regardless
of the pipe size.